Mount Street, Sydney

Mount Street, Sydney

“An Essential Services inspection for Fire Dampers as per AS1851 was carried out to all levels throughout the commercial office building. The majority of the fire dampers found failed to drop due to corrosion heavy corrosion years of building  movement that cause the duct to buckle hence stoping fire damper blades to freely drop. A full itemised cost analysis with photos was produced

Installation works carried out included: The decommissioning of all existing 23 mechanical fire dampers before each was replaced with an intumescent fire damper. Passive First  installation was done in accordance with AS1682.2 complete with an annual maintenance fire damper schedule and labels required under AS4072.1 & AS1851. A compliance certificate at the completion of works was also provided”

Back